South Korea · 6 mm² Cu XLPE; 3 loaded; B2; 40°C; 2 bunched circuits
44 × 0.91 × 0.80 = 32.032 AThe 30°C single-circuit reference is reduced for warmer air and grouped circuits.
Enter a tool name or topic.
Select the installation country before calculating: South Korea uses KEC-referenced KS tables and the USA uses NEC 2023 reference conditions. Korean sizes use mm²; US sizes use AWG or kcmil. Enter essential values first, then expand installation conditions and calculation details when needed.
Choose a task. Inputs stay in this page only.
Size and ampacity use the selected country. Voltage drop and DC loss use approximate formulas in mm²; AWG, ambient and conductor temperatures are not copied as equivalent values.
The 30°C single-circuit reference is reduced for warmer air and grouped circuits.
Load current is about 16.88 A. Select the supported 20 A rating, then the smallest cable rated at least 20 A under these conditions. Special loads need separate protection selection.
The DC formula counts the outgoing and return cable paths (2 × I × L × R).
Estimate round-trip conductor resistance and resistive watt loss on a DC circuit. Enter actual resistivity for the conductor material and temperature; connections are excluded.